Accessories
4.8 Residual current devices
3VA molded case circuit breakers with IEC certificate
392 Manual, 03/2019, A5E03603177010-03
A special "ADVANCED" residual current device has been developed for use with 3VA2
molded case circuit breakers.
Advanced RCD820
The RCD820 series is suitable for use in applications with exacting technical requirements:
High residual current response values
Long delay time settings for selective grading
Onboard interface to a fieldbus communication system
Graded alarm system
Features
The key features of the RCD820 series are:
Residual current devices available with ratings up to 630 A
Type A
Response current I
Δn
adjustable in ten steps from 0.03 A to 30 A
Delay time Δt adjustable in ten steps from 0 to 10000 ms
3 and 4-pole versions
LEDs to signal "ready" state, pre-alarms and communication status
Auxiliary contacts for tripped signals and pre-alarms
With remote acknowledgement and remote commissioning capability
Remote tripping possible via communication link or auxiliary contact
Suitable for use in 1-phase and 3-phase systems
Suitable for use as a display unit only