6 Order No.: A5E00999820-05
Technical data
Measuring inputs:
Only for connection to AC voltage systems
Frequency of the relative funda-
mental
50 / 60 Hz
Automatic setting
Waveform Sine or distorted
AC voltage input - Device with multi-range power supply
Phase-to-neutral voltage V
ph-n
AC 3~ 400 V (+ 20%), max. 347 V for UL
Phase-to-phase voltage V
ph-ph
AC 3~ 690 V (+ 20%), max. 600 V for UL
AC voltage input - Device with extra-low voltage power supply
Phase-to-neutral voltage V
ph-n
289 V 3 AC (+ 20%)
Phase-to-phase voltage V
ph-ph
500 V 3 AC (+ 20%)
Measuring category (in accordance with IEC 61010 Part 1)
Input voltage V
I
V
I
up to 230 V (V
ph-n
) CAT III
V
I
up to 400 V (U
ph-ph
) CAT III
V
I
up to 289 V (V
ph-n
) CAT III
V
I
up to 500 V (U
ph-ph
) CAT III
V
I
up to 400 V (V
ph-n
), max. 347 V for UL CAT III
(not for device with extra-low voltage power sup-
ply)
V
I
up to 690 V (V
ph-ph
), max. 600 V for UL CAT III
(not for device with extra-low voltage power sup-
ply)
AC current inputs
Only for connecting to axterlal current transformers
Input current I
I
AC 3~ x / 1 A (+ 20%, max. 300 V) or
AC 3~ x / 5 A (+ 20%, max. 300 V)
Surge withstand capability 100 A for 1 s
Measuring accuracy:
Voltage ± 0.3 %
Current ± 0.2 %
Power ± 0.5 %
Frequency ± 0.05 %
Power factor ± 0.5 %
Active energy Class 0.5S acc. to
IEC 62053-22:2003-01
Reactive energy Class 2 acc. to IEC 62053-23:2003-01
In the case of measurement on external current or voltage transformers the accuracy
of the measurement depends on the quality of the transformers.
Digital input:
Number 1 input
Input voltage
Rated value 24 V DC
Maximum input voltage 30 V DC
Switching thresh. signal "1" > 11 V DC
Input current
For signal "1" typ. 7 mA
Digital output:
Number 1 output
External power supply 12 ... 24 V DC
Max. switched output voltage 30 V DC
Output current
For signal "1" 10 ... 27 mA
Continuous load max. 100 mA
Transient overload max. 300 mA, for 100 ms
Resistive load 100 mA
For signal "0" max. 0.2 mA
Switching frequency 17 Hz
Short-circuit protection Yes
Supply voltage:
Rated range
AC/DC multi-range power
supply
95 … 240 V AC (50 / 60 Hz) or
110 … 340 V DC
Extra-low voltage power sup-
ply DC
DC 24 V, 48 V and 60 V or
DC 22 ... 65 V
Operating range ± 10% of rated range AC
± 10% of rated range DC
Power consumption Typically 8 VA (with optional expansion module)
Overvoltage category CAT III
Connection components:
Measuring inputs and supply
voltage
Screw terminals V
1
, V
2
, V
3
, V
N
, L/+, N/-
IL1(°k, l ), IL2(°k, l ), IL3(°k, l )
1-wire or 2-wire connection possible
Single-core 1 x 0.5 ... 4.0 mm², AWG 1 x 20 ... 12
2 x 0.5 ... 2.5 mm², AWG 2 x 20 ... 14
Finely stranded with end
sleeve
1 x 0.5 ... 2.5 mm², AWG 1 x 20 ... 14
2 x 0.5 ... 1.5 mm², AWG 2 x 20 ... 16
Stripped length 10 mm
Terminal screws
Tightening torque 0.8 ... 1.2 Nm, 7 ... 10.3 lbf in
Ring lug terminals V
1
, V
2
, V
3
, V
N
, L/+, N/-
IL1(°k, l ), IL2(°k, l ), IL3(°k, l )
Terminal studs M3 ... M4, #5 ...#8
Cable cross section depend-
ing on the ring lug used
1.0 ... 6.0 mm², AWG 18 ...10
The country-specific standards for ring lugs must be complied with, e.g. UL listed
under ZMVV /7, CSA, DIN 46237, IEC 60352-2.
Please observe the instructions of the lug manufacturer and IEC 60352-2 regard-
ing suitable crimp connections. The ring tongues must be installed parallel to
each other.
Connection screws
Tightening torque 0.8 ... 1.2 Nm, 7 ... 10.3 lbf in
max. vertical screw force 30 N, 6.75 lbf
Tools Screwdriver PZ2 cal. ISO 6789
Crimping tool in accordance with EN 60947-1
Digital output, digital input
Screw terminal , DI–, DI+, DO–, DO+
Single-core 1 x 0.2 ... 2.5 mm²
2 x 0.2 ... 1.0 mm²
Finely stranded without end
sleeve
1 x 0.5 ... 2.5 mm²
2 x 0.5 ... 1.5 mm²
Finely stranded with end
sleeve without plastic sleeve
1 x 0.25 ... 2.5 mm²
2 x 0.25 ... 1.0 mm²
Finely stranded with end
sleeve with plastic sleeve
1 x 0.25 ... 2.5 mm²
Finely stranded with TWIN
end sleeve with plastic sleeve
2 x 0.5 ... 1.5 mm²
AWG cables 1 x 24 ... 12
Stripped length 7 mm
Terminal screws
Tightening torque 0.5 ... 0.6 Nm
Tools Screwdriver PZ1 cal. ISO 6789
Crimping tool in accordance with EN 60947-1
Housing
Housing design Switching panel housing to IEC 61554
Housing dimensions W x H x D 96 mm x 96 mm x 51 mm
Mounting depth 51 mm
Maximum permissible thickness of
the switching panel for installation
max. 4 mm
Weight
Power Monitoring Device approx. 325 g
incl. packaging approx. 460 g
Mounting position The mounting position is vertical
Protection class Protection class II when installed
Degree of protection according to
IEC 60529
Front IP65
Rear side, device with
screw terminal
IP20, NEMA 1A
Rear side, device with ring lug
terminal
IP10 - higher requirements regarding the degree
of protection are only possible if suitable mea-
sures are taken by the customer.
Ambient conditions:
The device is suitable for switch panel mounting in accordance with IEC 61554. Oper-
ation is only permissible inside an enclosed dry room.
Temperature range
Operating temperature – 10 °C … + 55 °C
Storage and transport tem-
perature
–25°C … + 70°C
Relative atmospheric humidity 95 % at 25 °C without condensation
(normal conditions)
Operating altitude above sea level Up to 2000 m
Degree of contamination 2
Safety regulations
The device has been tested in accordance with the following standards:
IEC / UL 61010-1:2001 (2nd Ed.) with Corr. 1
CAN / CSA C22.2 No. 61010-1, second edition
EN 61010-1-1:2001 (2nd Ed.)
DIN EN 61010-1:2002 with Amendment 1