Parameters
6
6.1 Parameter types
Denition
You dene and thereby inuence the functions supported by the module operation of the I/O
module via the parameter types.
6.2 Module/channel parameters
Denition
Module/channel parameters are specic parameters whose conguration can aect the entire
module or channel.
Description
The following module/channel parameters are available:
Note
Unused channels
Deactivate unused channels in the conguration to improve the cycle time of the module. A
deactivated channel always returns the output value 0 mA.
Parameter Value range Default Parameter re‐
assignment in
RUN
Eciency range
Channel activated
(Page 20)
• Activated
• Deactivated
Activated Yes Channel
Diagnostics: No supply volt‐
age L+ (Page 21)
• Activated
• Deactivated
Activated Yes Module
Diagnostics, Wire break
1
(Page 21)
• Activated
• Deactivated
Activated Yes Channel
Wire break check
2
(Page 21)
• Activated
• Deactivated
Activated Yes Channel
DI 8x24...125VDC HA