Cause Solution
0xE1 0x01 Reserved bit set Check and correct the parameters
0xE1 0x02 Invalid diagnostics enable bit set for operating mode
0xE1 0x03 Invalid hardware interrupt enable bit set for operating
mode
0xE1 0x07 Invalid coding for input delay
0xE1 0x0E Invalid redundancy parameter assignment
Valid parameters
Only the values speci󹪝ed in the following are permitted. Values that are not listed are rejected
by the module.
Every parameter data record is checked by the module. If an incorrect parameter is detected, the
entire data record is rejected and the parameters of the module remain unchanged.
A.2 Parameter assignment and structure of the module/channel
parameters
Structure of data record 128
Data record 128 is 28 bytes long.
It contains module parameters as well as all channel parameters of the 8 channels.
Parameters, diagnostics messages and address space
A.2 Parameter assignment and structure of the module/channel parameters
DI 8x24...125VDC HA
34 Equipment Manual, 10/2021, A5E39288633-AD