Article number 6DL1131-6DF00-0PK0
Input characteristic curve in accordance with IEC
61131, type 3
Yes
Time stamping Yes; Resolution 10 ms
Time stamp (with precision of 1 ms) Yes; Resolution 1ms
Input voltage
• for signal "0"
-125 ... +5 V
• for signal "1"
+11 ... +125 V
Cable length
• shielded, max.
1 000 m
• unshielded, max.
600 m
Encoder
Connectable encoders
• 2-wire sensor
Yes
– permissible quiescent current (2-wire
sensor), max.
1.5 mA
Diagnoses
• Diagnostic information readable
Yes
• Monitoring the supply voltage
Yes
• Group error
Yes
Diagnostics indication LED
• MAINT LED
Yes; Yellow LED
• Monitoring of the supply voltage (PWR-LED)
Yes; green PWR LED
• Channel status display
Yes; green LED
• for channel diagnostics
Yes; red LED
• for module diagnostics
Yes; green/red DIAG LED
Potential separation
Potential separation channels
• between the channels
No
• between the channels and backplane bus
Yes
Permissible potential dierence
between dierent circuits 250 V AC/300 V DC
Isolation
Isolation tested with 3 500 V DC/1 min, type test
Ambient conditions
Ambient temperature during operation
• horizontal installation, min.
-40 °C
• horizontal installation, max.
70 °C
• vertical installation, min.
-40 °C
• vertical installation, max.
60 °C
Dimensions
Height 115 mm
Depth 138 mm
Technical specications
DI 8x24...125VDC HA