Installing and connecting
2.3 Safety instructions for connection
Active field distributors AFD4, AFD4 (FM), AFD8 and AFS
16 Product Information, 02/2015, A5E03775304-AC
Zone 2: Disconnecting the main line / connecting the main line to AFS
DANGER
Explosion hazard
In hazardous area
Zone 2
, you are not permitted to disconnect lines from an AFS during
operation.
Before you start the work, disconnect the FDC 157 coupler(s) from the voltage.