EasyManua.ls Logo

Siemens SIMATIC AFD4 - Figure 2-8 Terminal Block AFD4; AFD4 (FM); AFD8

Siemens SIMATIC AFD4
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installing and connecting
2.4 Connecting the field bus to the active field distributors AFD4 / AFD4 (FM) / AFD8
Active field distributors AFD4, AFD4 (FM), AFD8 and AFS
20 Product Information, 02/2015, A5E03775304-AC
Terminal assignment
Connect the wires of the bus cables using the screw-type terminals on the terminal block.
Figure 2-8 Terminal block AFD4 / AFD4 (FM) / AFD8
Table 2- 1 Terminal assignment on the active field distributor AFD4 / AFD4 (FM) / AFD8
Connection
Terminal
Assignment
T1, T2 Main line
+
Data line
-
Data line
S1 to S4 / S8 Spur line to the field devices
+
Data line
-
Data line
Basic procedure
1. Prepare the bus cable.
2. Connect the bus cable:
Open the field distributor.
Connect the wires to the terminal block.
Close the field distributor.
Preparation of the AFD4 (FM)
Note
Replace blanking caps with UL
- or CSA-approved lead-throughs for connection of additional
field devices.
The customer must use a screwed gland and a cable as specified for the application
according to
NEC and CEC. The installation must conform to the relevant requirements of
the National Electrical Code® (ANSI/NFPA
-70 (NEC®).
Requirement
Active field distributor is mounted and grounded.

Table of Contents