Installing and Wiring the C7-635
3-24
C7-635 Control System
A5E00155581-04
3.6 Connecting Shielded Cables
Overview
This section describes how to connect the shield of shielded signal lines to the
ground. A grounding terminal is used to connect the shield directly to the ground of
the C7-635.
Procedure
Proceed as follows to install the grounding terminal supplied with the C7-635 and
the shield terminals:
1. Mount the grounding busbar at the position shown in Fig. 3-17, using the
included screws
1 or, as an alternative, at this position 2 .
2. Install the shielding terminals on the grounding busbar as shown in Fig. 3-17.
3. Push the stripped ends of the cable shielding into the shielding terminals.
Shielding
terminal
Functional
ground
2
2
1
Figure 3-17 C7-635 with grounding busbar, shielding terminals, and terminal for functional ground