EasyManua.ls Logo

Siemens SIMATIC C7-635 - Page 80

Siemens SIMATIC C7-635
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Specifications
A-18
C7-635 Control System
A5E00155581-04
Analog inputs
Number
Number of inputs
Current / voltage input
Resistance input
4 channels
1 channel
Cable length
Shielded Maximum 100 m (109 yd.)
Voltage, Currents, Potentials
Resistance input
No-load voltage 2.5 V, typically
Measured current 1.8 mA to 3.3 mA, typically
Galvanic isolation
Between channels and I/O
bus
Yes
Between channels No
Permissible potential difference
Between inputs and MANA
(VCM)
8.0 VDC
Between MANA and Minternal
(VISO)
75 VDC/60 VAC
Insulation tested at 500 VDC
Analog Value Generation
Measuring principle Momentary value encoding
(successive approximation)
Integration time/conversion time/tesolution (per channel)
Configurable Yes
Integration time in ms 2.5 / 16.6 / 20
Permissible input frequency Maximum 400 Hz
Resolution (including
overdrive)
11 bits + sign bit
Suppression of interference
frequency f1
400 / 60 / 50 Hz
Time constant of the input filter 0.38 ms
Basic execution time 1 ms

Table of Contents