EasyManua.ls Logo

Siemens SIMATIC ET 200pro - Quick guide to commissioning; 2.1 Introduction and aim of the example

Siemens SIMATIC ET 200pro
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting and connecting
4.3 Connecting the connection module CM CPU 2PN M12 7/8"
CPU 1516pro-2 PN (6ES7516-2PN00-0AB0)
28 Operating Instructions, 11/2019, A5E35873416-AC
M12 circular socket X2-P1:
Autocrossing is always active. As a result, the M12 circular socket has either a device
assignment (MDI) or switch assignment (MDI-X).
View of M12 connector, d-
coded (PROFINET)
Terminal
MDI (device assignment)
MDI-X (switch assignment)
Assignment
Assignment
X1 P1 R, X1 P2 R, X2 P1 for connection of PROFINET
1
TD_P (Transmit Data +)
RD_P (Receive Data +)
2
RD_P (Receive Data +)
TD_P (Transmit Data +)
3
TD_N (Transmit Data –)
RD_N (Receive Data –)
4
RD_N (Receive Data –)
TD_N (Transmit Data –)
Thread Functional ground
Pin assignment of the 7/8" connector
View of 7/8" connector (supply voltage 1L+ und
2L+)
Terminal
Assignment
X3 DC 24 V for infeed
X4 DC 24 V for loop-through
1
Load voltage ground 2M
2
Ground for electronics/encoder supply 1M
3
Functional ground
4
Electronic / encoder supply 1L+
5 Load voltage supply 2L+

Table of Contents

Other manuals for Siemens SIMATIC ET 200pro

Related product manuals