Commissioning
8.2 Procedure for commissioning the ET 200pro distributed I/O system with CPU
CPU 1516pro-2 PN (6ES7516-2PN00-0AB0)
Operating Instructions, 11/2019, A5E35873416-AC
73
Commissioning procedure
To commission the ET 200pro distributed I/O system as IO controller on PROFINET IO,
proceed as follows:
Table 8- 1 Procedure for commissioning the ET 200pro as an IO controller on PROFINET IO
1 Mounting ET 200pro (with CPU 1516pro-2 PN) Section Mounting and connecting (Page 23)
Operating instructions ET 200pro Distributed I/O
System
(
https://support.industry.siemens.com/cs/ww/en/view/
2 Inserting the SIMATICmemory card into IO controller Section Inserting/replacing SIMATIC memory card
3 Connecting the ET 200pro
• Supply voltages
• PROFINET IO
• Sensors and actuators
Section Mounting and connecting (Page 23)
Operating instructions ET 200pro Distributed I/O
System
(
https://support.industry.siemens.com/cs/ww/en/view/
21210852)
Configuring the IO controller
1
Section Configuring the CPU (Page 34)
Switch on supply voltages for the IO controller
Section Mounting and connecting (Page 23)
Switch on supply voltages for IO devices
Documentation of the IO device
Download configuration to the IO controller
Switch IO controller to RUN mode
Section RUN mode (Page 81)
9 Check LEDs Section Interrupts, diagnostics, error messages and
10 Test inputs and outputs The following functions are helpful: Monitoring and
modifying tags, testing with program status, forcing,
controlling the outputs. See section Test and service
1
The IO devices are configured with the IO controller.