EasyManua.ls Logo

Siemens SIMATIC HMI OP3 - Modifying the Address in MPI Network Configuration

Siemens SIMATIC HMI OP3
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10-3
Operator Panel OP3
Edition 11/99
To set the modes, proceed as follows:
1. Choose the standard screen System Mode.
2. Set the mode you require by means of a symbolic input.
3. After you confirm your input by pressing ENTER, a warm restart is
performed.
10.4 Modifying the Address in MPI Network Configuration
You can set and modify the address of the OP3 in the MPI network
configuration by means of a standard screen. To do so, proceed as follows:
1. Choose the standard screen System MPI Address.
2. Modify the OP address and, if necessary, the baud rate.
3. After you confirm your input by pressing ENTER, a warm restart is
performed.
Procedure
Settings with
standard screens
Procedure
S
y
stem Settin
g
s on Standard Screens

Table of Contents

Related product manuals