192 Operating Instructions, 03/2012, A5E03404994-02
Memory
HMI devices
KP400 C
omfort
KTP400
Comfort
KP700
Comfort
TP700
Comfort
KP900
Comfort
TP900
Comfort
KP1200
Comfort
TP1200
Comfort
Usable memory for
application data
4 MB 12 MB
Usable memory for recipe
data
1
512 KB 2 MB
Additional memory for
options
4 MB 12 MB
Memory card 2 x MMC/SD combination slot
1
Can be extended via memory card
Interfaces
HMI devices
KP400 C
omfort
KTP400
Comfort
KP700
Comfort
TP700
Comfort
KP900
Comfort
TP900
Comfort
KP1200
Comfort
TP1200
Comfort
1 x RS 422/485 (PROFIBUS) Max. 12 Mbps, applies to DP operations
Ethernet (PROFINET) 1 x RJ45 10/100
Mbps
2 x RJ45 10/100 Mbps
1
Audio - Line In and Line Out
USB 2.0 1 x Host
2)
1 x Device
3)
2 x Host
2
1 x Device
3
1
With integrated switch (one IP address only)
2
USB type A, maximum load 500 mA, equivalent to USB standard 2.0
3
USB type Mini B (5-pin), equivalent to USB standard 2.0
Power supply
HMI devices
KP400 C
omfort
KTP400
Comfort
KP700
Comfort
TP700
Comfort
KP900
Comfort
TP900
Comfort
KP1200
Comfort
TP1200
Comfort
Rated voltage
Permissible voltage range
24 V DC
+19.2 V to +28.8 V
Rated current 0.13 A 0.5 A 0.75 A 0.85 A
Inrush current I
2
t 0.5 A
2
s
Power 3.1 W 12 W 18 W 20 W
Maximum permissible
transient
35 V (500 ms)
Minimum time between two
transients
50 s
Internal protection Electronic