EasyManua.ls Logo

Siemens SIMATIC KP400 Comfort - Connecting a USB Device

Siemens SIMATIC KP400 Comfort
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting and connecting the HMI device
3.3 Connecting the device
Comfort Panels
Operating Instructions, 03/2012, A5E03404994-02
49
3.3.6 Connecting a USB device
Below are examples of devices you can connect to the USB type A interfaces of the HMI
device:
External mouse
External keyboard
Printer
USB memory stick
Industrial USB Hub 4
Industrial USB hub 4 can be obtained using order number 6AV6671-3AH00-0AX0.
Note when connecting
NOTICE
USB type A interface not suitable for commissioning
The USB type A interface is only intended for connecting peripheral devices.
Do not use the USB type A interface for commissioning or maintenance.
USB 2.0 certified cable required
If you use a USB cable which is not USB 2.0 certified, errors may occur during data
transfer.
Use only USB cables that are labeled "Certified HI-SPEED USB 2.0".
USB cable length maximum 1.5 m
USB cables with lengths more than 1.5 m do not ensure secure data transfer.
The cable may not be longer than 1.5 m.
Functional problem with USB port
If you connect an external device with a 230 V power supply to the USB port without using
an non-insulated installation, you may experience functional problems.
Use a non-insulated system design.
Excessive rated load on port
A USB device with too high a power load may possibly cause functional problems.
Observe the values for the maximum load of the USB interface. You will find the values in
the section "Technical specifications" (Page 207).