EasyManua.ls Logo

Siemens SIMATIC NET CP 343-1 ERPC - Page 17

Siemens SIMATIC NET CP 343-1 ERPC
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and commissioning
3.2 Procedure for installation and commissioning
CP 343-1 ERPC
Manual, 03/2010, C79000-G8976-C239-02
17
Step Execution Meaning / explanation
Install the CP on the S7 standard rail.
Establish the connection via the enclosed bus
connector to the backplane bus.
Slots 4 to 11 are permitted for the CP in racks 0 to 3
(connected by IM 360/361).
Proceed as described in the sections dealing with setup and
wiring, explained in detail in /10/.
1
Note
The CP cannot be used in an extension rack that is connected via the IM 365! Reason: The required
communication bus is not connected to the extension rack via the IM 365.
Connect the CP to the power supply. Follow the steps as described in detail in /10/ when wiring
between the power supply and the CPU.
2
Notes
The CPU, CP and IM (if one exists) must be connected to the same power supply.
Only wire up the S7300 / C7300 with the power switched off!
3 Connect the CP to Industrial Ethernet. Connector behind the hinged front panel
An Ethernet cable can also be inserted and removed with the
power supply on.
4 Optional:
connect the ERP subscribers to the same
Industrial Ethernet network.
This step is only necessary if you want to use ERPC functions.
5 Optional:
Download the ERPC firmware to the CP.
This step is only necessary if you want to use ERPC functions.
Read the relevant documentation of our cooperation partners
ILS Technology LLC.
6 The remaining steps in commissioning involve
downloading the STEP 7 configuration data.
To download the STEP 7 configuration, you can connect the
PG as follows:
via MPI
via Industrial Ethernet
Addressing the first time
(IP address assignment / node initialization)
Downloading the defined configuration
For further details, refer to the general Part A of this
manual.
The PG/PC requires a LAN attachment, for example via a CP
1613 and must have the necessary software (for example the
S71613 package or SOFTNET IE). The TCP/IP protocol must
be installed. The protocol used must then be applied to the
S7ONLINE access point.

Table of Contents

Related product manuals