EasyManua.ls Logo

Siemens SIMATIC OEM PP32 - Digital Inputs and Outputs

Siemens SIMATIC OEM PP32
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A-2
OEM
Push Button Panel Equipment Manual
Release 08/98
OEM PP32/OP17OEM PP32Ambient conditions
Shock loading
S Operation
S Shipping, storage
15 g/11 msec
25 g/6 msec
Vibration
S Operation
S Shipping, storage
0.075 mm (10 Hz ... 58 Hz)
1 g (58 Hz ... 500 Hz)
3.5 mm (5 Hz ... 10 Hz)
1 g (10 Hz ... 500 Hz)
Max. pressure difference (front/rear sides) 2hPa
Barometric pressure
S Operation
S Shipping, storage
706 to1030 hPa
581 to 1030 hPa
The conformity of the product described with the regulations of Directive 89/336 EEC is proved by com-
pliance with the following standards:
Interference immunity EN 50082-1 OEM PP32 OEM PP32/OP17
Static discharge (contact discharge) EN 61000-4-2 Class 3
RF irradiation EN 61000-4-3 Class 3
Pulse modulation ENV 50204 (900 MHz ”5 MHz)
RF conduction ENV 50141 Class 3
Burst interference ENV 61000-4-4 Class 3
Radio interference EN 50081-2 OEM PP32 OEM PP32/OP17
RFI suppression EN 55011 Class A
A.2 Digital inputs and outputs
24 V digital inputs OEM PP32 OEM PP32/OP17
Power supply
S Rated value
S Permissible range
S Value at t < 0.5 s
+ 24 V DC
+18.0 ... +30.0 V
35 V
Connectable Key, switch (inductive load not permissible)
Number of inputs 16
Potential isolation from internal circuitry
Input voltage
S Rated value
S with signal “0”
S with signal “1”
24 V DC
0 ... 5 V
15 ... 30 V
Technical Data

Related product manuals