Functions
4.2 PGN parameters
SIMATIC PN/J1939 LINK
20 Operating Instructions, 12/2018, A5E45307564-AA
Priority PGN output n bytes
PGN output proxy
Priority 0 … 7 Message priority
Transmit event Cyclic PGN is sent with the time interval set in
the "Transmission cycle" parameter. In
"Cyclic" mode, standard messages and
the Broadcast Announce Message
Change of
value
PGN is sent when the data value
changes. All transport protocols are
Remote re-
quest
PGN is sent when a request is made
from another device in the J1939 net-
work. The request has PGN 59904.
Standard messages and CMDT are
Transport proto-
col
Standard mes-
PGN message with up to 8 bytes data
Broadcast
Announce
Fragmented transmission of data with
more than 8 bytes without flow control.
Connection
Mode Data
Transfer
Fragmented transmission of data with
more than 8 bytes with flow control.
Transmission
10 to 5000 Transmission cycle is only valid if "cy-
clic" is configured as send event.
Reception cycle
in ms
PGN input n bytes
PGN input proxy
0 to 5000 If a PGN is not received in time, a diag-
nostics alarm is sent to the S7 controller.
The value 0 means that the functionality