Instructions
9.2 PID_3Step
PID control
Function Manual, 03/2017, A5E35300227-AC
333
If State = 0, then ENO = FALSE.
If State ≠ 0, then ENO = TRUE.
Automatic switchover of operating mode during commissioning
Automatic mode is activated following successful pretuning or fine tuning. The following table
shows how Mode and State change during successful pretuning.
1 1 4 Set ModeActivate = TRUE
1 4 1 Value of State is saved in Mode parameter
n 4 1 Pretuning successfully completed
Automatic mode is started
PID_3Step automatically switches the operating mode in the event of an error. The following
table shows how Mode and State change during pretuning with errors.
1 4 1 Value of State is saved in Mode parameter
If ActivateRecoverMode = TRUE, the operating mode that is saved in the Mode parameter is
activated. At the start of transition time measurement, pretuning, or fine tuning, PID_3Step
saved the value of State in the Mode in/out parameter. PID_3Step therefore switches to the
operating mode from which transition time measurement or tuning was started.
If ActivateRecoverMode = FALSE, "Inactive" or "Approach substitute output value" mode is
activated.
Automatic switchover of operating mode after transition time measurement
If ActivateRecoverMode = TRUE, the operating mode that is saved in the Mode parameter is
activated after successful transition time measurement.
If ActivateRecoverMode = FALSE, the system switches to "Inactive" operating mode after
successful transition time measurement.