EasyManua.ls Logo

Siemens SIMATIC S7-1200

Siemens SIMATIC S7-1200
527 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instructions
9.4 PID basic functions
PID control
472 Function Manual, 03/2017, A5E35300227-AC
9.4.4.2
Mode of operation TCONT_CP
Setpoint branch
The setpoint is entered at input SP_INT in floating-point format as a physical value or
percentage. The setpoint and process value used to form the control deviation must have the
same unit.
Process value options (PVPER_ON)
Depending on PVPER_ON, the process value can be read in, in the I/O or floating-point
format.
PVPER_ON
Process Value Input
TRUE The process value is read in via the analog I/Os
(PIW xxx) at input PV_PER.
FALSE The process value is acquired in floating-point
format at input PV_IN.
Process value format conversion CRP_IN (PER_MODE)
The CRP_IN function converts the I/O value PV_PER to floating-point format depending on
the PER_MODE switch according to the following rules:
PER_MODE
Output of CRP_IN
Analog Input Type
Unit
0 PV_PER * 0.1 Thermoelements;
PT100/NI100; standard
°C;°F
1
PV_PER * 0.01
PT100/NI100; climate;
°C;°F
2
PV_PER * 100/27648
Voltage/current
%
Process value scaling PV_NORM (PF_FAC, PV_OFFS)
The PV_NORM function calculates the output of CRP_IN according to the following rule:
"Output of PV_NORM" = "Output of CRP_IN)" * PV_FAC + PV_OFFS
It can be used for the following purposes:
Process value adjustment with PV_FAC as process value factor and PV_OFFS as
process value offset.
Scaling of temperature to percentage
You want to enter the setpoint as a percentage and must now convert the measured
temperature value to a percentage.
Scaling of percentage to temperature
You want to enter the setpoint in the physical temperature unit and must now convert the
measured voltage/current value to a temperature.

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals