EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 426

Siemens SIMATIC S7-1200
527 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instructions
9.3 PID_Temp
PID control
426 Function Manual, 03/2017, A5E35300227-AC
Tag
Data type
Default
Description
Retain.CtrlParams.Heat
.ControlZone
REAL 3.402822e+38 Active control zone width for heating
The control zone for heating is switched off with
Heat.ControlZone = 3.402822e+38.
Heat.ControlZone is only set automatically during pretun-
ing heating or pretuning heating and cooling if PIDSelf-
Tune.SUT.TuneRuleHeat = 2 is selected as method of the
parameter calculation.
For controllers with deactivated cooling output (Con-
fig.ActivateCooling = FALSE) or controllers with activated
cooling output and cooling factor (Config
.AdvancedCooling = FALSE), the control zone is symmet-
rically located between Setpoint Heat.ControlZone and
Setpoint + Heat.ControlZone.
For controllers with activated cooling output and PID pa-
rameter switching (Config.ActivateCooling = TRUE, Config
.AdvancedCooling = TRUE), the control zone is located
between Setpoint Heat.ControlZone and Setpoint +
Cool.ControlZone.
Heat.ControlZone is retentive.
Heat.ControlZone > 0.0
Retain.CtrlParams.Heat
.DeadZone
REAL 0.0 Active dead zone width for heating (see PID parameters
(Page 174))
The dead zone for heating is switched off with
Heat.DeadZone = 0.0.
Heat.DeadZone is not set automatically or adjusted during
tuning. You must correctly configure Heat.DeadZone
manually.
When the dead zone is switched on, the result can be a
permanent control deviation (deviation between setpoint
and process value). This can have a negative effect on
fine tuning.
For controllers with deactivated cooling output (Config
.ActivateCooling = FALSE) or controllers with activated
cooling output and cooling factor (Config
.AdvancedCooling = FALSE), the dead zone is symmetri-
cally located between Setpoint Heat.DeadZone and
Setpoint + Heat.DeadZone.
For controllers with activated cooling output and PID pa-
rameter switching (Config.ActivateCooling = TRUE, Config
.AdvancedCooling = TRUE), the dead zone is located
between Setpoint Heat.DeadZone and Setpoint +
Cool.DeadZone.
Heat.DeadZone is retentive.
Heat.DeadZone ≥ 0.0
Retain.CtrlParams.Cool.Gain REAL 1.0 Active proportional gain for cooling
Cool.Gain is retentive.
Only effective if the cooling output and PID parameter
switching are activated (Config.ActivateCooling = TRUE
and Config.AdvancedCooling = TRUE).
Cool.Gain ≥ 0.0

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals