EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 429

Siemens SIMATIC S7-1200
527 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instructions
9.3 PID_Temp
PID control
Function Manual, 03/2017, A5E35300227-AC
429
Tag
Data type
Default
Description
Retain.CtrlParams.Cool
.ControlZone
REAL 3.402822e+38 Active control zone width for cooling
The control zone for cooling is switched off with
Cool.ControlZone = 3.402822e+38.
Cool.ControlZone is only set automatically during pretun-
ing cooling or pretuning heating and cooling if PIDSelf-
Tune.SUT.TuneRuleCool = 2 is selected as method of the
parameter calculation.
Cool.ControlZone is retentive.
Only effective if the cooling output and PID parameter
switching are activated (Config.ActivateCooling = TRUE
and Config.AdvancedCooling = TRUE).
Cool.ControlZone > 0.0
Retain.CtrlParams.Cool
.DeadZone
REAL 0.0 Active dead zone width for cooling (see PID parameters
(Page 174))
The dead zone for cooling is switched off with
Cool.DeadZone = 0.0.
Cool.DeadZone is not set automatically or adjusted during
tuning. You must correctly configure Cool.DeadZone
manually.
When the dead zone is switched on, the result can be a
permanent control deviation (deviation between setpoint
and process value). This can have a negative effect on
fine tuning.
Cool.DeadZone is retentive.
Only effective if the cooling output and PID parameter
switching are activated (Config.ActivateCooling = TRUE
and Config.AdvancedCooling = TRUE).
Cool.DeadZone ≥ 0.0
Note
Change the tags listed in this
table in "Inactive" mode to prevent malfunction of the PID
controller.
See also
PID_Temp ActivateRecoverMode tag (Page 442)
PID_Temp Warning tag (Page 444)
Multi-zone controlling with PID_Temp (Page 199)

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals