Configuration Variants of the S7-400
6-11
Automation System S7-400 Configuration and Use
A5E0044271 1-02
Interfacing Rules
Interface modules are divided into send IMs and receive IMs A send IM sends
signals to the connected expansion device, the corresponding receive IM receives
and forwards the signals. The following rules apply to connecting interface
modules:
The send IM must always be located in the central controller.
You can connect up to four receive IM to one send IM.
Up to six send IMs can be installed in the central controller .
Maximum of 22 Racks
Interfacing with send and receive IMs, you can connect up to 21 expansion devices
to a central controller .