Cycle and Response Times of the S7-400
9.4 Communication Load
S7-400 Automation System, CPU Specifications
9-10 Manual, 10/2006, 6ES7498-8AA04-8BA0
Dependency of the Actual Cycle Time on the Communication Load
The following figure describes the non-linear dependency of the actual cycle time on the
communication load. This example uses a cycle time of 10 ms.
0 % 10 % 20 % 30 % 40 % 50 % 60 %
10 ms
20 ms
25 ms
15 ms
5 ms
30 ms
5 %
Cycle time
You can set the communication load in this range
Communication load
Figure 9-6 Dependency of the Cycle Time on the Communication Load
Further Effect on the Actual Cycle Time
Due to the increase in the cycle time as a result of the communications component, even
more asynchronous events occur, from a statistical point of view, within an OB 1 cycle than,
say, interrupts. This also increases the OB 1 cycle. This extension depends on the number
of events that occur per OB 1 cycle and the time required to process these events.
Notes
Check the effects of a change of the value for the parameter "Cycle load due to
communications" in system operation.
The communication load must be taken into account when you set the maximum cycle
time, since time errors will occur if it is not.
Recommendations
If possible, apply the default value.
Use a larger value only if the CPU is being used primarily for communication purposes
and the user program is non-time-critical. In all other cases select a smaller value.