Technical specifications
10.3 Technical Specification of the CPU 416-3F PN/DP; (6ES7416-3FR05-0AB0)
S7-400 Automation System, CPU Specifications
10-32 Manual, 10/2006, 6ES7498-8AA04-8BA0
CPU and firmware version
Communication
PG/OP communication Yes
Number of connectable OPs 63 with message processing
Number of connection resources for S7
connections via all interfaces and CPs
64, with one each of those reserved for
programming device and OP
Global data communication Yes
Number of GD circuits
Max. 16
Number of GD packets
Transmitters
Receiving stations
Max. 16
Max. 32
Size of GD packets
Of which consistent
Max. 64 bytes
1 variable
S7 basic communication Yes
MPI Mode
Via SFC X_SEND, X_RCV, X_GET and X_PUT
DP Master Mode
Via SFC I_GET and I_PUT
User data per job
Of which consistent
Max. 76 bytes
1 variable
S7 communication Yes
User data per job
Of which consistent
Max. 64 KB
1 variable (462 bytes)
S5-compatible communication Via FC AG_SEND and AG_RECV, max. via 10
CP 443-1 or 443-5)
User data per job
Of which consistent
Max. 8 KB
240 bytes
Standard communication (FMS) Yes (via CP and loadable FB)
Web Server Yes
Open IE communication via TCP/IP
Number of connections / access points, total max. 30
TCP/IP Yes (via integrated PROFINET interface and
loadable FBs)
Maximum number of
connections
30
Data length, max.
32767 bytes
ISO on TCP Yes (via integrated PROFINET interface or CP
443-1 EX 41 and loadable FBs)
Maximum number of
connections
30
Max. data length via integrated
PROFINET interface
32767 bytes
Max. data length via CP 443-1
EX 41
1452 bytes
UDP
Maximum number of
connections
30
Data length, max.
1472 bytes