EasyManua.ls Logo

Siemens SIMATIC TI500 - Command 66 - Read K Memory; Command 67 - Read WY Memory; C-33 Command 66 - Request; C-34 Command 66 - Response

Siemens SIMATIC TI500
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus Commands
C-27
TIWAY I Gateway User Manual
This
command permits the collection of constant (K) memory
. The formats of
the command and response are as follows.
I000000
Request: aa 42 llll nnnn XXXX
Checksum (XXXX)
Number of locations to collect (nnnn)
Starting location to collect from (llll)
Command 66 (42 hex)
Address (aa)
Figur
e C-33
Command
66 — Request
I000000
Response: aa 42 bb dddd . . . XXXX
Checksum (XXXX)
K-memory data
Number of data bytes to follow (bb)
Command 66 (42 hex)
PLC TIWAY network address (aa)
Figur
e C-34
Command
66 — Response
This command permits the collection of W
ord Output memory
. The formats
of the command and response are as follows.
I000000
Request: aa 43 llll nnnn XXXX
Checksum (XXXX)
Number of locations to collect (nnnn)
Starting location to collect from (llll)
Command 67 (43 hex)
Address (aa)
Figur
e C-35
Command
67 — Request
I000000
Response: aa 43 bb dddd . . . XXXX
Checksum (XXXX)
WY memory data
Number of data bytes to follow (bb)
Command 67 (43 hex)
PLC TIWAY network address (aa)
Figur
e C-36
Command
67 — Response
Command 66 —
Read K Memory
Command 67 —
Read WY Memory

Table of Contents