Page #16 background imageLoading...
Page #16 background image
Product Overview
1.2 Application of ET 200pro fail-safe modules
ET 200pro Distributed I/O System - Fail-Safe Modules
16 Operating Instructions, 05/2007, A5E00394073-02
Application Limited to Safety Mode
You can operate standard and fail-safe modules simultaneously in an ET 200pro.
Fail-safe modules can only be used in safety mode. They cannot be operated in standard
mode.
Achievable Safety Classes
Fail-safe modules are equipped with integrated safety functions for safety mode.
The following safety classes can be achieved by assigning applicable parameters to the
safety functions in
STEP 7
with the
S7 Distributed Safety
or
S7 F/FH Systems
optional
package, combining certain standard and F-modules and arranging the wiring of the sensors
and actuators in a specific way:
Table 1-1 Achievable Safety Classes in Safety Mode
Safety class in safety mode
In accordance with IEC
61508
In accordance with EN 954-1 In accordance with Performance
Level (PL)
SIL2 Category 3 d
SIL3 Category 3 e
SIL3 Category 4 e
See also
Configuration of ET 200pro with Fail-Safe Modules (Page 19)

Table of Contents

Other manuals for Siemens SIMATIC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC and is the answer not in the manual?

Siemens SIMATIC Specifications

General IconGeneral
Product type designationSIMATIC
CPUVaries by model
MemoryVaries by model
Input/OutputVaries by model
CommunicationVaries by model
Programming LanguageSTEP 7
Operating Temperature0°C to 60°C (varies by model)
Protection ClassIP20
CategoryProgrammable Logic Controller (PLC)