63
2.8 Measured Values
Measured values
Measuring
path
1
Menu Tolerances
2
Voltage
L1-N, L2-N,
L3-N, (N-E)
d a h
± 0.2%
Voltage
L1-L2, L2-L3,
L3-L1, Σ
3
d a h
± 0.2%
Current
L1, L2, L3, N,
Σ
3
d a h
± 0.2%
Active power P
+ import, - export
L1, L2, L3, Σ
d a h
± 0.5%
Reactive power Q
+ cap, - ind
L1, L2, L3, Σ
d a h
± 0.5%
Apparent power S
L1, L2, L3, Σ
d a h
± 0.5%
Power factor |cosϕ|
4
L1, L2, L3, Σ
d a h
± 0.5%
Active power factor
cosϕ
4
L1, L2, L3, Σ
d a h
± 0.5%
Phase angle
4
L1, L2, L3, Σ
d a h
±
Frequency
5
L1-N
d a h
± 10 mHz
Active power import
L1, L2, L3, Σ
d a
± 0.5%
Active power export
L1, L2, L3, Σ
d a
± 0.5%
Active power absolute
L1, L2, L3, Σ
d a
± 0.5%
Active power saldo
Σ
d a
± 0.5%
Reactive power cap
L1, L2, L3, Σ
d a
± 0.5%
Reactive power ind
L1, L2, L3, Σ
d a
± 0.5%