SINUMERIK 840C / SIMODRIVE 611–D (DA)
165071 Rotor resistance (MD x138) illegal OK softkey
Softkey ”Calculate controller data (MSD only)”
The controller data have been calculated, the machine data concerned has been given a suitable default value.
The value 0 has been entered for the rotor resistance (MD 1138 and MD 2138).
If necessary, correct value and repeat function.
Applies as from SW 5.4
165072 Moment of inertia (MD x117) illegal OK softkey
Softkey ”Calculate controller data”
The controller data have been calculated, the machine data concerned has been given a suitable default value.
The value 0 has been entered for the moment of inertia (MD 1117 and MD 2117).
If necessary, correct value and repeat function.
Applies as from SW 5.4
165073 Maximum speed smaller than field weakening speed OK softkey
Softkey ”Calculate controller data (MSD only)”
The controller data have been calculated, the machine data concerned has been given a suitable default value.
The maximum speed (MD 1146 and MD 2146) is smaller than the field weakening speed (MD 1142 and MD 2142).
If necessary, correct value and repeat function.
Applies as from SW 5.4
165074 Field weakening speed (MD x142) not allowed OK softkey
Softkey ”Calculate controller data (MSD only)”
The controller data have been calculated, the machine data concerned has been given a suitable default value.
The value 0 has been entered for the field weakening speed (MD 1142 and MD 2142).
If necessary, correct value and repeat function.
Applies as from SW 5.4
165075 No-load current (MD 1118) not allowed OK softkey
Softkey ”Calculate controller data (FDD only)”
The controller data have been calculated, the machine data concerned has been given a suitable default value.
The value 0 has been entered for the no-load current.
If necessary, correct value and repeat function.
Applies as from SW 5.4
165076 Ratio maximum current / no-load current illegal OK softkey
Softkey ”Calculate controller data (FDD only)”
The controller data have been calculated, the machine data concerned has been given a suitable default value.
The ratio maximum current (MD 1104) no-load current (MD 1118) exceeds 900.
If necessary, correct value and repeat function.
Applies as from SW 5.4
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
1 Alarms
1.5.1 Alarm description