611V3usa.PPT
Sheet 3/3  -  8/10/98
1) Tighten DC Link Screws (Torx T-20) 1.8Nm (16in-lbs)
2) Commutating Reactor should be located as close as
  possible to the I/R Module.  
3) Fuses - Not supplied with system:
        Module     Rated Input   Suggested        Suggested
         Rating        Current      Siemens Fuse   Fuseholder
          5 KW           12.5 A           3NA3805        3NH4030
        10 KW           24    A           3NA3810        3NH4030
        28 KW           65    A           3NA3824        3NH4030
        16 KW           27    A           3NA3814        3NH4030
        36 KW           60.5 A           3NA3824        3NH4030
        55 KW           92.5 A           3NA3832        3NH4030
        80 KW         134    A           3NA3136        3NH4230
      120 KW         202    A           3NA3144        3NH4230 
 
4) Voltage measurements should be balanced when 
     checked; Line to Line and Line to Ground .
5)  Alternate Fuse location. [ Note that different fuse ratings 
     may be required at this location vs the fuses in note 3) ]  
6)  Transformer must have an Impedance Voltage rating of  >1% , < 3% .
NOTE: Applies to: 16, 36, 55, 80 & 120 KW I/R Modules Only
In applications where a Contactor, Disconnect, etc., might be
opened while the Drive’s I/R Module is in the DC Bus Regulating 
Mode, the Infeed/Regeneration Module must be disabled 
(terminal 48 or 63) => 10ms  prior to the opening of the line 
contacts.  If this instruction is not adhered to,  I/R module damage
could result.  In cases of “brown-out” or loss of Power Company 
power, a complete circuit remains to absorb the regenerative
energy and failures should not occur.
7)
8) The I/R Module  input voltage must be derived from a TN-C, (Wye
     connection with Neutral Ground,) system.  If configuration and
     voltage specifications are according to requirements, a matching
     transformer is not required.  See Planning Guide for Details.
8.1) If line configuration is not TN-C, an isolation transformer with
   neutral ground connection is required.  See Planning Guide for
  proper sizing and configuration details.
 8.2) If line configuration  is TN-C, an auto transformer can be used
  to provide correct input voltage.
2 @ 60W x 120VAC
Voltmeter
Machine
Ground
U1, V1 or W1
on I/R - U/E
    Module
To verify TN-C line neutral connection  is present, connect
meter as shown and note reading.  When lightbulb assembly
is connected, reading should not change and bulbs should
glow normally.  Note:  Terminal 48 must be disabled
611-A V3 Power & Grounding Notes
Section A  Power & Grounding
9) Terminals L1-L2 are only available for the 80 and 120KW I/R 
     modules only. F1-F2 fuses should be greater than or equal to 4A 
     depending upon the maximum cable cross-section. If the input 
     voltage fails or F1-F2 fuses blow, the I/R module pulses are 
     disabled and the internal line contactor drops out. The I/R module
     will display the line fault LED, and the ready relay and the internal 
     line contactor contacts will drop out. Terminal 48 must be de-
     energized and can be re-energized again after >1 sec. or if the 
     power is turned off and on again. In this case, the jumper between
     terminals 9 & 48 must be removed and a switch inserted. The 
     switch is not required if the system is powered off and on again 
     using the main supply circuit breaker.
 
A*   Shield connections must be made on both sides of
        power cables using the highest possible area.
B*   Each Power Section must have separate leads from the
        terminal “  “  to the machine ground bus.