EasyManuals Logo

Siemens SIMODRIVE 611A User Manual

Siemens SIMODRIVE 611A
329 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #167 background imageLoading...
Page #167 background image
611V3usa.PPT
Sheet 3/3 - 8/10/98
1) Tighten DC Link Screws (Torx T-20) 1.8Nm (16in-lbs)
2) Commutating Reactor should be located as close as
possible to the I/R Module.
3) Fuses - Not supplied with system:
Module Rated Input Suggested Suggested
Rating Current Siemens Fuse Fuseholder
5 KW 12.5 A 3NA3805 3NH4030
10 KW 24 A 3NA3810 3NH4030
28 KW 65 A 3NA3824 3NH4030
16 KW 27 A 3NA3814 3NH4030
36 KW 60.5 A 3NA3824 3NH4030
55 KW 92.5 A 3NA3832 3NH4030
80 KW 134 A 3NA3136 3NH4230
120 KW 202 A 3NA3144 3NH4230
4) Voltage measurements should be balanced when
checked; Line to Line and Line to Ground .
5) Alternate Fuse location. [ Note that different fuse ratings
may be required at this location vs the fuses in note 3) ]
6) Transformer must have an Impedance Voltage rating of >1% , < 3% .
NOTE: Applies to: 16, 36, 55, 80 & 120 KW I/R Modules Only
In applications where a Contactor, Disconnect, etc., might be
opened while the Drive’s I/R Module is in the DC Bus Regulating
Mode, the Infeed/Regeneration Module must be disabled
(terminal 48 or 63) => 10ms prior to the opening of the line
contacts. If this instruction is not adhered to, I/R module damage
could result. In cases of “brown-out” or loss of Power Company
power, a complete circuit remains to absorb the regenerative
energy and failures should not occur.
7)
8) The I/R Module input voltage must be derived from a TN-C, (Wye
connection with Neutral Ground,) system. If configuration and
voltage specifications are according to requirements, a matching
transformer is not required. See Planning Guide for Details.
8.1) If line configuration is not TN-C, an isolation transformer with
neutral ground connection is required. See Planning Guide for
proper sizing and configuration details.
8.2) If line configuration is TN-C, an auto transformer can be used
to provide correct input voltage.
2 @ 60W x 120VAC
Voltmeter
Machine
Ground
U1, V1 or W1
on I/R - U/E
Module
To verify TN-C line neutral connection is present, connect
meter as shown and note reading. When lightbulb assembly
is connected, reading should not change and bulbs should
glow normally. Note: Terminal 48 must be disabled
611-A V3 Power & Grounding Notes
Section A Power & Grounding
9) Terminals L1-L2 are only available for the 80 and 120KW I/R
modules only. F1-F2 fuses should be greater than or equal to 4A
depending upon the maximum cable cross-section. If the input
voltage fails or F1-F2 fuses blow, the I/R module pulses are
disabled and the internal line contactor drops out. The I/R module
will display the line fault LED, and the ready relay and the internal
line contactor contacts will drop out. Terminal 48 must be de-
energized and can be re-energized again after >1 sec. or if the
power is turned off and on again. In this case, the jumper between
terminals 9 & 48 must be removed and a switch inserted. The
switch is not required if the system is powered off and on again
using the main supply circuit breaker.
A* Shield connections must be made on both sides of
power cables using the highest possible area.
B* Each Power Section must have separate leads from the
terminal “ “ to the machine ground bus.
1-167

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMODRIVE 611A and is the answer not in the manual?

Siemens SIMODRIVE 611A Specifications

General IconGeneral
BrandSiemens
ModelSIMODRIVE 611A
CategoryInverter
LanguageEnglish

Related product manuals