7
02.98
1-73
Siemens AG 1998 All Rights reserved 6SN1197–0AA00 02.98 Edition
SIMODRIVE 611 (PJ)
Function overview and settings using the parameter board
6SN1114–0AA01–0AA1
Table 7-1
Parameter
Value range Setting elements
Speed controller
Integral action time
Proportional gain
Adaptation:
Integral action time
Proportional gain
Adaptation range
T
N
= 7...43 ms
Kp = 2...150
T
Nadap
/T
N
= 0.04...1
Kp
adap
/Kp = 4...35
n
x2
– n
x1
= 0 – 0...(65 – 330) mV
Front panel potentiometer T
N
, additionally
C2
Front panel potentiometer Kp, additionally
R50
R34 and front panel potentiometer ADAP
R38
R40
Drift compensation (offset) –30...+30 mV (referred to n
set
) Front potentiometer, drift
Direction of rotation reversal Cw/ccw for pos. n
set
S2.1
Tachometer adaptation V
tach.
= 40...15 V/n
rated
Switch S1; additionally R6, R7, R8
Tachometer adjustment n
actN
= 2.2...0.7 n
act
(n
act
= 10 V/n
rated
)
Front panel potentiometer tachometer; ad-
ditionally R3 and R10
Speed setpoint adaptation
(speed reduction)
100 % 11...5V= n
actN
or
(only term.56/14)
10 V =
n
actN
1...100
R5
Inhibit I component Speed controller without
I component
Terminal 6
Limit I component, speed
controller
I component fully effective ... inef-
fective
R52
Current controller
Adaptation, motor/power module
Current actual value normalization
Current controller gain
I
max
= 23...100 % I
limit
Kp(I) = 0.5...11.5;
S2.2....S2.5
S2.6...S2.9; additionally R15, if K
p
(I) > 11.5
Current setpoint adaptation I
max
= 10...0 V R42
Inhibit I component in current–
controlled operation
Current controller without I compo-
nent
R1
Select current–controlled operation offline
online via terminal 22
S2.10
R14
Master/slave operation Up to 5 slave modules Terminals 258, S2.10, R42, R44
Response threshold, I
2
t limiting,
reduction
6...55 % I
limit
R9
Monitoring time, speed controller at
its endstop
26...1200 ms R54
Monitoring, speed controller at its
endstop
ON OFF R32
External current setpoint limiting
(e. g. travel to endstop)
1...100 % I
max
Speed controller monitoring OFF
Terminal 96 (variable); R12 (fixed)
Current limiting after the monitoring
time, speed controller at its endstop
1...100 % I
max
R2, R32
Current limiting after the I
2
t timer has
expired
Refer to I
2
t limiting in the
Start–up Guide
R2/R32
Torque limiting for setting–up opera-
tion via terminal 112 (NE module)
1...100 % I
max
Speed controller monitoring OFF
R12
Electrical weight equalization I
set,
suppl.
= 0...50 % I
max
R46/R48
7.1.1 Function overview and settings using the parameter board