Siemens SIMOTICS 1PQ8 - Faults at the External Fan

Siemens SIMOTICS 1PQ8
166 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.11.4 Faults at the external fan
The following table shows the possible causes of and remedial measures for faults on forced-
ventilated machines.
Table 8-3 Cooling system faults
↓ High temperature rise with load
Possible causes of faults Remedial measures
X Wrong direction of rotation of the external fan Check the electrical connections to the external fan.
X External fan is not running Check the external fan and its connections.
X Reduced air flow Check the air ducts; clean the machine.
See also
Connecting an external fan motor (Page 86)
Operation
8.11 faults
SIMOTICS TN Series N-compact 1PQ8
Operating Instructions 11/2018 107