EasyManua.ls Logo

Siemens SIMOTION CX32-2

Siemens SIMOTION CX32-2
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Supplementary system components
6.4 CBE30-2 Ethernet communication board
SIMOTION D4x5-2
110 Manual, 02/2012
Interface assignment
Table 6- 14 X1400 interface
Representation Pin Name Signal type Description
1 TXP Output Ethernet transmit differential signal
2 TXN Output Ethernet transmit differential signal
3 RXP Input Ethernet receive differential signal
4 -- 4 together with 5 via 75 ohm at the 1 nF capacitor to the
shield ground
5 -- 4 together with 5 via 75 ohm at the 1 nF capacitor to the
shield ground
6 RXN Input Ethernet receive differential signal
7 -- 7 together with 8 via 75 ohm at the 1 nF capacitor to the
shield ground
8 -- 7 together with 8 via 75 ohm at the 1 nF capacitor to the
shield ground
Screened
backshell
M_EXT Screen, permanently connected
Position of the ports
The interfaces are located on the front side of the CBE30-2.
Figure 6-10 CBE30-2 interface