Meaning LED displays
SF
(red)
5 VDC
(green)
RUN
(green)
STOPU
(yellow)
STOP
(yellow)
BUS1F
(red)
BUS2F
(red)
Request for overall reset by the SIMOTION C or
via the mode selector of the SIMOTION C
x 1 0 0 0.5/1 x x
Overall reset in progress 1 1 1 1 1 1 1
Overall reset completed x 1 0 0 1 x x
SIMOTION Kernel update in progress
(only for SIMOTION C230-2)
→ 1 → → → → →
SIMOTION Kernel update completed
(only for SIMOTION C230-2)
x 1 0 0 1 x x
SIMOTION C240 without micro memory card 1 1 0 1 1 1 1
Copy SIMOTION Kernel to micro memory card 0.5/1 1 0.5/1 0.5/1 0.5/1 0.5/1 0.5/1
SIMOTION C is operating without error 0 1 x x x 0 0
An event that can be acknowledged (alarm, mes‐
sage, note) is present
1 1 x x x x x
Fault to which the user program cannot respond
The following actions may be required to rectify
the fault:
● Switch Off/On
● Check micro memory card
● Re-commissioning
● Replacement of SIMOTION C
x 1 x ☆ ☆ ☆ ☆
No license exists for technology/option objects
which require a license
0.5/1 1 x x x x x
SIMOTION - STOP state
User program is running at a breakpoint
x 1 0.5/1 1 1 x x
PROFIBUS DP interface as slave
Bus fault
Searching for baud rate
x 1 x x x 1 1
Parameterization error
No cyclic data exchange
x 1 x x x 0.5/1 0.5/1
Cyclic data exchange x 1 x x x 0 0
PROFIBUS DP interface as master
Bus fault (bus short-circuit) x 1 x x x 1 1
Bus fault (slaves have failed or cable break) x 1 x x x 0.5/1 0.5/1
No error or no interface configured x 1 x x x 0 0
Alarm, error, and system messages
10.2 Combinations of LED displays
SIMOTION C
Operating Instructions, 11/2016, A5E33441428B 161