EasyManua.ls Logo

Siemens simovert master drive - Page 17

Siemens simovert master drive
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.96 Transport, Unpacking, Installation
Siemens AG 6SE7087-6BM70
2-3
SIMOVERT MASTER DRIVES Operating Instructions
Equipment rooms must be dry and dust-free. Ambient and cooling air must not contain any electrically conductive
gases, vapors and dusts which could diminish the functionality. Dust-laden air must be filtered.
WARNING
When mounting in cabinets, a clearance of above and below must be provided so that the
cooling air flow is not restricted (refer to dimension drawings, Section 2.4).
Dimension the cabinet cooling in line with the power loss! (
+
Section „Technical data“)
The converter ambient climate in operating rooms may not exceed the values of code F according to DIN 40040.
For temperatures > 40 °C (104 °F) and installation altitudes > 1000 m, de-rating is required (
+
Section
„Technical data“).

Table of Contents

Related product manuals