EasyManua.ls Logo

Siemens simovert master drive - Replacing the Snubber Resistor; Replacing the IGBT Modules

Siemens simovert master drive
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.96 Maintenance
Siemens AG 6SE7087-6BM70
5-7
SIMOVERT MASTER DRIVES Operating Instructions
5.2.8 Replacing the snubber resistor
Remove the capacitors
Remove the SML- and SMU modules
Remove the module busbars
Release the mounting bolts (2 ×
M5, torque: max. 1.8 Nm) and remove the snubber resistor
A uniform coating of heat conducting paste must be applied to the resistor
Install the new snubber resistor in the inverse sequence.
5.2.8.1 Replacing the IGBT modules
Replace as for IGD, but additionally
Remove the mounting bolts of the defective IGBT modules and remove the
IGBT.
Install the new IGBT module. Observe the following:
Coat the module mounting surface with a
thin and uniform coating of
heat conducting paste.
Tighten-up the IGBT module mounting bolts with 3 Nm, observe the
sequence (Fig. 5.3).
1
2
34
5
6
CECE
Tighten-up the IGBT modules
1. By hand (
0,5 Nm),
sequence: 2 - 5 - 3 - 6 - 1 - 4
2. tighten-up with 3 Nm,
sequence: 2 - 5 - 3 - 6 - 1 - 4
Fig. 5.3 Tighten-up IGBT modules

Table of Contents

Related product manuals