12.96 Maintenance
Siemens AG 6SE7087-6BM70
5-7
SIMOVERT MASTER DRIVES Operating Instructions
5.2.8 Replacing the snubber resistor
Remove the capacitors
Remove the SML- and SMU modules
Remove the module busbars
Release the mounting bolts (2 ×
M5, torque: max. 1.8 Nm) and remove the snubber resistor
A uniform coating of heat conducting paste must be applied to the resistor
Install the new snubber resistor in the inverse sequence.
5.2.8.1 Replacing the IGBT modules
Replace as for IGD, but additionally
Remove the mounting bolts of the defective IGBT modules and remove the
IGBT.
Install the new IGBT module. Observe the following:
Coat the module mounting surface with a
thin and uniform coating of
heat conducting paste.
Tighten-up the IGBT module mounting bolts with 3 Nm, observe the
sequence (Fig. 5.3).
1
2
34
5
6
CECE
Tighten-up the IGBT modules
1. By hand (
0,5 Nm),
sequence: 2 - 5 - 3 - 6 - 1 - 4
2. tighten-up with 3 Nm,
sequence: 2 - 5 - 3 - 6 - 1 - 4
Fig. 5.3 Tighten-up IGBT modules

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simovert master drive and is the answer not in the manual?

Siemens simovert master drive Specifications

General IconGeneral
BrandSiemens
Modelsimovert master drive
CategoryInverter
LanguageEnglish

Related product manuals