08.96 Connecting-up
Siemens AG 6SE7087-6BM70
3-3
SIMOVERT MASTER DRIVES Operating Instructions
Supply side Motor side
Order Rated Cross-section Recommended fuse Rated Cross-section
No. DC North-America AC
Curr. VDE AWG Curr. VDE AWG
6SE70 (A) (mm
2
) MCM
1)
(A) Type Type (V) (A) (A) (mm
2
) MCM
Input voltage
DC 510 V to 620 V
Output voltage
3 AC 0 V to 620 V
35-1TJ20 607 4
×
300 4
×
800 2
×
450 2
×
3NE3233 2
×
170M6709 660 2
×
550 510 2
×
300 2
×
800
36-0TK20 702 4
×
300 4
×
800 2
×
560 2
×
3NE3335 2
×
170M6710 660 2
×
630 590 4
×
300 4
×
800
37-0TK20 821 4
×
300 4
×
800 2
×
560 2
×
3NE3335 2
×
170M6710 660 2
×
630 690 4
×
300 4
×
800
38-6TK20 1023 4
×
300 4
×
800 2
×
710 2
×
3NE3337-8 2
×
170M6711 660 2
×
700 860 4
×
300 4
×
800
41-1TK20 1309 6
×
300 6
×
800 2
×
800 2
×
3NE3338-8 1100 4
×
300 4
×
800
41-1TM20 1310 6
×
300 6
×
800 2
×
560 2
×
3NE3335 2
×
170M6710 660 2
×
650 1100 4
×
300 4
×
800
41-3TM20 1547 6
×
300 6
×
800 2
×
560 2
×
3NE3335 2
×
170M6710 660 2
×
650 1300 6
×
300 6
×
800
Input voltage
DC 675 V to 780 V
Output voltage
3 AC 0 V to 780 V
33-0UJ20 354 2
×
300 2
×
800 1
×
500 3NE3334-0B 170M5713 660 700 297 2
×
300 2
×
800
33-5UJ20 421 2
×
300 2
×
800 1
×
630 3NE3336 170M5713 660 700 354 2
×
300 2
×
800
34-5UK20 538 2
×
300 2
×
800 1
×
710 3NE3337-8 170M5714 660 900 452 2
×
300 2
×
800
35-7UK20 678 4
×
300 4
×
800 2
×
450 2
×
3NE3233 2
×
170M5712 660 2
×
630 570 2
×
300 2
×
800
36-5UK20 774 4
×
300 4
×
800 2
×
500 2
×
3NE3334-0B 2
×
170M5712 660 2
×
630 650 4
×
300 4
×
800
38-6UK20 1023 4
×
300 4
×
800 2
×
630 2
×
3NE3336 2
×
170M6712 660 2
×
800 860 4
×
300 4
×
800
41-0UM20 1178 6
×
300 6
×
800 1
×
710 3NE3337-8 170M5714 660 900 990 4
×
300 4
×
800
41-1UM20 1285 6
×
300 6
×
800 2
×
450 2
×
3NE3233 2
×
170M5712 660 2
×
630 1080 4
×
300 4
×
800
41-2UM20 1464 6
×
300 6
×
800 2
×
500 2
×
3NE3334-0B 2
×
170M5712 660 2
×
630 1230 6
×
800 6
×
800
41-4UM20 1666 6
×
300 6
×
800 2
×
630 2
×
3NE3336 2
×
170M6712 660 2
×
800 1400 6
×
800 6
×
800
41-6UM20 1880 8
×
300 8
×
800 2
×
630 2
×
3NE3336 2
×
170M6712 660 2
×
800 1580 6
×
800 6
×
800
Input voltage
DC 890 V to 930 V
Output voltage
3 AC 0 V to 930 V
33-0WJ20 354 2
×
300 2
×
800 1
×
500 3NE3334-0B 170M5713 660 700 297 2
×
300 2
×
800
33-5WJ20 421 2
×
300 2
×
800 1
×
630 3NE3336 170M5713 660 700 354 2
×
300 2
×
800
34-5WK20 538 2
×
300 2
×
800 1
×
710 3NE3337-8 170M5714 660 900 452 2
×
300 2
×
800
35-7WK20 678 4
×
300 4
×
800 2
×
450 2
×
3NE3233 2
×
170M5712 660 2
×
630 570 2
×
300 2
×
800
36-5WK20 774 4
×
300 4
×
800 2
×
500 2
×
3NE3334-0B 2
×
170M5712 660 2
×
630 650 4
×
300 4
×
800
38-6WK20 1023 4
×
300 4
×
800 2
×
630 2
×
3NE3336 2
×
170M6712 660 2
×
800 860 4
×
300 4
×
800
41-0WM20 1178 6
×
300 6
×
800 1
×
710 3NE3337-8 170M5714 660 900 990 4
×
300 4
×
800
41-1WM20 1285 6
×
300 6
×
800 2
×
450 2
×
3NE3233 2
×
170M5712 660 2
×
630 1080 4
×
300 4
×
800
41-2WM20 1464 6
×
300 6
×
800 2
×
500 2
×
3NE3334-0B 2
×
170M5712 660 2
×
630 1230 6
×
800 6
×
800
41-4WM20 1666 6
×
300 6
×
800 2
×
630 2
×
3NE3336 2
×
170M6712 660 2
×
800 1400 6
×
800 6
×
800
41-6WM20 1880 8
×
300 8
×
800 2
×
630 2
×
3NE3336 2
×
170M6712 660 2
×
800 1580 6
×
800 6
×
800
NOTES
♦ Current- and voltage data in this table are rated values
♦ The cables to the drive converter are protected using fuses with gL characteristics.
♦ The cross-sections are determined for three-core copper cables, routed horizontally in air at 30 °C (86°F)
ambient temperature (according to DIN VDE 0298 Part 2 / Group 5) and the recommended cable protection
according to DIN VDE 0100 Part 430.
♦ AWG (American Wire Gauge): American wire gauge for cross sections up to 120 mm
2
;
♦ MCM (Mille Circular Mil): American wire gauge for cross-sections above 120 mm
2.
Table 3.1 Connection cross-sections and fusibles