Technical Data 12.96
9-2 Siemens AG 6SE7087-6BM70
SIMOVERT MASTER DRIVES Operating Instructions
Inverter types 6SE70... 35-1TJ20 36-0TK20 37-0TK20 38-6TK20 41-1TK20 41-1TM20 41-3TM20
Rated voltage, rated frequency, rated current
Rated voltage in V
n
Input
Output
V
DC 510 ... 620 ±15 %
3 AC 0 ... Rated voltage / 1.35
Rated frequency f
n
Input
Output: U/f = konst
U = konst
Hz
0 ... 600
8 ... 300
Rated current I
n
Input
Output
A
607
510
702
590
821
690
1023
860
1309
1100
1309
1100
1547
1300
DC link voltage V
dn
V = Rated voltage
Rated output kVA 336...406 388...470 454...550 566...685 724...876 724...876 856...1036
Auxiliary power supply
DC 24 V (20 V - 30 V)
A 5 without Options;
with Options refer to
Section 6.1
5 + 3 without Options;
with Options refer to
Section 6.1
Auxiliary power supply V AC 230
±
15%
Loading Class II acc. to EN 60146-1-1
Rated current A 464 538 628 783 1001 1001 1183
Base load time s 240
Overcurrent A 694 802 938 1169 1496 1496 1768
Overcurrent time s 60
Losses, cooling, power factor
Power factor
Converter cos
ϕ
U
<
0.92 ind.
<
0.92 ind.
<
0.92 ind.
<
0.92 ind.
<
0.92 ind.
<
0.92 ind.
<
0.92 ind.
Efficiency
η
−
Pulse frequency 2.5 kHz 0.98 0.98 0.98 0.98 0.98 0.98 0.98
Power loss
−
Pulse frequency 2.5 kHz
kW
6 8 9 10161517
Required cooling air flow m
3
/s 0.6 0.75 0.75 0.75 0.92 1.5 1.5
Pressure drop
∆
p Pa 350 640 640 640 950 640 640
Sound pressure level, dimensions, weights
Sound pressure level dB(A) 80 83 83 83 85 85 85
Type JKKKKMM
Width for IP00
Height
Depth
mm 800
1400
550
800
1750
550
800
1750
550
800
1790
550
800
1790
550
2300
1910
580
2300
1910
580
Ground
− IP00
kg
350 520 520 520 535 ca. 1500 ca. 1500
Required current for fan (typical)
230 V / 50 Hz A 2.6 5.2 5.2 5.2 13.4 10.4 10.4
230 V / 60 Hz A 3.4 6.7 6.7 6.7 20.0 13.4 13.4