Configuring the terminal block
5.5 Analog outputs
Inverter with CU240B-2 and CU240E-2 Control Units
102 Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Table 5- 12 Additional analog output settings
Parameter
p07xx[0]: AO 0
p07xx[1]: AO 1
Description
p0773[x] Analog outputs smoothing time constant
Smoothing time constant of 1st order low-pass filter for the analog outputs
p0775[x] Activate absolute-value generation
0: No absolute-value generation (factory setting)
1. The absolute value of the analog output is used.
If the original value was negative, the corresponding bit is set in the status word of
the analog input (r0785).
p0782[x] Analog outputs signal source for inverting
Signal source to invert the analog output signals