Technical data
10.3 Technical data, Power Modules
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
273
Table 10- 11 Frame size A, 3-ph. 380 V … 480 V AC, ± 10 % - Part 2
Order number with filter, IP20
without filter, IP20
with filter, PT
without filter, PT
6SL3210-1PE14-3AL0
6SL3210-1PE14-3UL0
---
---
6SL3210-1PE16-1AL0
6SL3210-1PE16-1UL0
6SL3211-1PE16-1AL0
---
---
6SL3210-1PE18-0UL0
__
6SL3210-1PE18-0UL0
Values based on Low Overload
● LO power
● LO input current
● LO output current
1.5 kW
5.5 A
4.1 A
2.2 kW
7.7 A
5.9 A
3 kW
10.1 A
7.7 A
Values based on High Overload
● HO power
● HO input current
● HO output current
1.1 kW
4.7 A
3.1 A
1.5
6.1 A
4.1 A
2.2 kW
8.8 A
5.9 A
General values
● Power loss
● Fuse
● Cooling air requirement IP20
PT
● Cable cross-section for line and
motor connection
● Torque for line and motor and
motor connection
● Weight filtered, IP20
unfiltered, IP20
filtered, PT
unfiltered, PT
0.07 kW
3NA3 803 (10 A)
5 l/s
---
1.0 … 2.5 mm
2
0.5 Nm
1.5 kg
1.4 kg
---
---
0.1 kW
1)
3NA3 803 (10 A)
5 l/s
7 l/s
1.5 … 2.5 mm
2
0.5 Nm
1.5 kg
1.4 kg
1.8 kg
---
0.12 kW
2)
3NA3 805 (16 A)
5 l/s
7 l/s
1.5 … 2.5 mm
2
0.5 Nm
---
1.4 kg
---
1.7 kg
1) for PT devices 0.08 kW above the heat sink;
2) for PT devices 0.1 kW above the heat sink