Technical data
10.3 Technical data, Power Modules
Inverter with CU240B-2 and CU240E-2 Control Units
278 Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Performance dependent data, PM250-2
Table 10- 16 Frame sizes A, 3-ph. 380 V … 480 V AC, ± 10 % - Part 1
Order No. with filter, IP20
without filter, IP20
6SL3210-1QE11-8AL0
6SL3210-1QE11-8UL0
6SL3210-1QE12-3AL0
6SL3210-1QE12-3UL0
6SL3210-1QE13-2AL0
6SL3210-1QE13-2UL0
Values based on Low Overload
● LO power
● LO input current
● LO output current
0.55 kW
1.9 A
1.7 A
0.75 kW
2.4 A
2.2 A
1.1 kW
3.3 A
3.1 A
Values based on High Overload
● HO power
● HO input current
● HO output current
0.37 kW
1.7 A
1.3 A
0.55 kW
2.1 A
1.7 A
0.75 kW
2.7 A
2.2 A
General values
● Power loss
● Fuse
● Cooling air requirement
● Cable cross-section for line and
motor connection
● Torque for line and
motor connection
● Weight with filter
without filter
0.05 kW
3NA3 801 (6 A)
5 l/s
1.0 … 2.5 mm
2
0.5 Nm
1.5 kg
1.4 kg
0.05 kW
3NA3 801 (6 A)
5 l/s
1.0 … 2.5 mm
2
0.5 Nm
1.5 kg
1.4 kg
0.06 kW
3NA3 801 (6 A)
5 l/s
1.0 … 2.5 mm
2
0.5 Nm
1.5 kg
1.4 kg