Technical data
6.6 690 V converters
Power Module PM240-2
104 Hardware Installation Manual, 01/2020, A5E33294624B AL
Table 6- 36 PM240-2, frame size G, 500 V … 690 V 3 AC
Article No. with filter
6SL3210-1PH31-7CL0
6SL3210-1PH32-1CL0
6SL3210-1PH32-5CL0
LO base load power 160 kW 200 kW 250 kW
LO base load input current 170 A 205 A 250 A
LO base load output current
171 A
208 A
250 A
HO base load power
132 kW
160 kW
200 kW
HO base load input current 160 A 185 A 225 A
HO base load output current
144 A
171 A
208 A
Fuse according to the IEC/UL
3NE1227-0 (250A)
3NE1230-0 (315A)
3NE1331-0 (350A)
Power loss
2.94 kW
3.70 kW
4.64 kW
Required cooling air flow
210 l/s
210 l/s
210 l/s
Weight
114 kg
114 kg
114 kg
6.6.3 Current derating depending on the pulse frequency, 690 V converters
Article number
LO power [kW]
Pulse frequency [kHz]
2 *)
4
LO base load output current [A]
6SL3210-1PH21-4 . L0
11
14
8.4
6SL3210-1PH22-0 . L0
15
19
11.4
6SL3210-1PH22-3 . L0
18.5
23
13.8
6SL3210-1PH22-7 . L0
22
27
16.2
6SL3210-1PH23-5 . L0
30
35
21
6SL321 . -1PH24-2 . L0
37
42
25.2
6SL3210-1PH25-2 . L0
45
52
31.2
6SL321 . -1PH26-2 . L0
55
62
37.2
6SL3210-1PH28-0 . L0
75
80
48
6SL3210-1PH31-0 . L0
90
100
60
6SL3210-1PH31-2 . L0
110
115
69
6SL3210-1PH31-4 . L0 132
142
85.2
6SL3210-1PH31-7CL0
160
171
102.6
6SL3210-1PH32-1CL0
200
208
124.8
6SL3210-1PH32-5CL0
250
250
150
*) Factory setting