Technical data
6.4 200 V converters
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
77
Load cycles and typical applications:
"Low Overload" load cycle
"High Overload" load cycle
The "Low Overload" load cycle assumes a
uniform base load with low
requirements
placed on brief accelerating phases. Typical
applications when designing according to
"Low Overload" include:
Pumps, fans and compressors
Wet or dry blasting technology
Mills, mixers, kneaders, crushers,
agitators
Basic spindles
Rotary kilns
Extruders
The "High Overload" load cycle permits
dynamic accelerating phases at a reduced
base load. Typical applications when de-
signing according to "High Overload" in-
clude:
Horizontal and vertical conveyor
technology (conveyor belts, roller
conveyors, chain conveyors)
Centrifuges
Escalators/moving stairways
Lifters/Lowerers
Elevators
Gantry cranes
Cable railways
Storage and retrieval machines
Typical converter load cycles
Figure 6-1 "Low Overload" and "High Overload" load cycles
6.4 200 V converters
Motors for 200 V Power Modules
For the 200 V Power Modules, induction motors are permissible in the range from
25% … 150% of the converter power without any restrictions.
Permissible motors
Note
Motors for converter operation
Only use
motors that are suitable for operation with converters with a DC link.