Technical data
6.4 200 V converters
Power Module PM240-2
78 Hardware Installation Manual, 01/2020, A5E33294624B AL
6.4.1 General data, 200 V converters
Line voltage FSA … FSC 200 V … 240 V 1 AC ± 10% 0.55 kW … 4 kW - LO
200 V … 240 V 3 AC ± 10% 0.55 kW … 7.5 kW - LO
0.37 kW … 5.5 kW - HO
FSD … FSF 200 V … 240 V 3 AC ± 10% (in
operation -20% < 1 min)
11 kW … 55 kW - LO
7,5 kW … 45 kW - HO
Line supply configurations
Grounded TN/TT line supplies or non-grounded IT line supplies
Permissible line supplies (Page 46)
Line impedance FSA … FSC
2% ≤ Uk < 4%. For Uk < 2%, we recommend a line reactor, or a Power Mod-
ule with the next higher power rating.
Power factor λ FSA … FSC
0.7 without line reactor for Uk ≥ 2%
0.85 with line reactor for Uk < 2%
0 V 3 AC … 0.95 × input voltage
0 … 550 Hz, depending on the control mode
< LO base load input current
Overvoltage category
according to EN 61800-5-
III for line supplies
Pulse frequency 4 kHz (factory setting),
Adjustable in steps of 2 kHz.
Current reduction as a function of the pulse frequency (Page 86)
If you increase the pulse frequency, the converter reduces the maximum output current.
Short-circuit current
(SCCR) and branch pro-
tection
Maximum permissible line short-circuit current ≤ 100 kA rms
Branch protection and short-circuit strength according to UL and IEC
(https://support.industry.siemens.com/cs/ww/en/view/109479152)
Degree of protection ac-
cording to EN 60529
IP20
IP55 PT devices outside the control cabinet
Protection class according
The converters are devices with protection class I
Touch protection accord-
DGUV regulation 3 when used for the intended purpose
Cooling in compliance with
Forced air cooling AF
Safety Integrated See function manual "Safety Integrated"
"Safety Integrated" function manual
(https://support.industry.siemens.com/cs/ww/en/view/109751320)