EasyManua.ls Logo

Siemens SINAMICS G120 - Pzd Send Signals Interconnection

Siemens SINAMICS G120
732 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication
Function diagrams
2-535
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Fig. 2-31 2450 – PZD send signals interconnection
- 2450 -
Function diagram
87654321
FP_2450_97_61.vsd
PROFIdrive / PROFIBUS
G120 CU230P-2 DP
13.12.2010 V4.4
PZD send signals interconnection
<1>
PZD send word 1...8
p2051[0...7] WORD
r2053[0...7] WORD
...
<1>
U16 -r2089[0]2 [2452]ZSW1
I16 4000 hex p2000r0063[0]6 -NIST_A
FAULT_CODE
U16
r2131301 [8060] U16
r2132303 [8065]WARN_CODE
U16r311358MELD_NAMUR -
4000 hex p2004I16r0082[1]54 [6799]PIST_GLATT
4000 hex p2003I16r0080[1]53 [6799]MIST_GLATT
4000 hex p2002I16r0068[1]51 [6799]IAIST_GLATT
4000 hex p2000I16r0063[1]57 -NIST_A_GLATT
PROFIBUS
Signal sources for PZD send signals
Signal
PROFIdrive
Signal No.
Interconnection
parameter
Function
diagram
Data type
Scaling
Status word 1
Actual speed A (16 bit)
Absolute actual current, smoothed
Actual torque smoothed
Power factor, smoothed
Actual speed, smoothed
VIK-NAMUR message bit bar
Fault code
Alarm code
PROFIdrive send
telegram
Header
Data
Telegram assignment
according to p0922
[2420]
Trailer
Data type according to the PROFIdrive profile: I16 = Integer16, U16 = Unsigned16.
Description
U16r0053305 [2454]ZSW3
Status word 3

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals