EasyManua.ls Logo

Siemens SINAMICS G120 - Status Word, Faults;Alarms 1 and

Siemens SINAMICS G120
732 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Internal control/status words
Function diagrams
2-565
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Fig. 2-59 2548 – Status word, faults/alarms 1 and 2
- 2548 -
Function diagram
87654321
FP_2548_97_61.vsd
Internal control/status words
G120 CU230P-2
13.12.2010 V4.4
Status word, faults/alarms 1 and 2
0
...
11
0
r2139.3
r2139.7
r2135.14
r2135.15
r2135.13
r2135.12
1
2
r2139.0
r2139.6
r2139.8
4
5
6
7
8
12
13
14
15
9
10
3
From the fault buffer [8060.6]
From the alarm buffer [8065.4]
From the thermal monitoring, motor [8016.8]
From the thermal monitoring, power module [8014.8]
From the thermal monitoring, motor [8016.8]
From the thermal monitoring, motor [8016.8]
Status word, faults/alarms 1
Bit
No.
1 = Acknowledgement running
1 = Fault present
1 = Internal signal 1 present
1 = Alarm present
1 = Internal signal 2 present
Reserved
Reserved
Reserved
Reserved
Status word, faults/alarms 2
Bit
No.
1 = Fault motor overtemperature
1 = Fault, thermal overload, power module
1 = Alarm motor overtemperature
1 = Alarm, thermal overload, power module
ZSW fault/alarm 1
r2139
r2139
ZSW fault/alarm 2
r2135
r2135
Reserved
r2139.1111
Alarm class bit 0
r2139.1212
Alarm class bit 1
13 - 15