EasyManua.ls Logo

Siemens SINAMICS G120 - Page 545

Siemens SINAMICS G120
732 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication
Function diagrams
2-545
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Fig. 2-40 9208 – Send telegram, free PDO mapping (p8744 = 2)
- 9208 -
Function diagram
87654321
FP_9208_97_68.vsd
CANopen
G120 CU230P-2 CAN
13.12.2010 V4.4
Send telegram, free PDO mapping (p8744 = 2)
...
<1>
.
.
.
COB-ID
<1>
TPDO 1
TPDO 2
TPDO 8
CANopen send words 1 ... 8
Send buffer
PZD send word
1
PZD send word
2
PZD send word
3
PZD send word
4
PZD send word
5
PZD send word
6
PZD send word
7
PZD send word
8
Automatic assignment of the
send buffer to the TPDOs
The assignment is made
from send buffer 1 and
from TPDO 1.
Objects that occur a
multiple number of times
are updated from the
same send buffer.
Object
1
Object
2
Object
3
Object
4
Object
1
Object
2
Object
3
Object
4
Object
1
Object
2
Object
3
Object
4
Transmit PDO 2
p8721
Mapping TPDO 2
p8731
Transmit PDO 8
p8727
Mapping TPDO 8
p8737
Object
1
Object
4
Sub-D socket
CAN bus
TPDO: Transmit Process Data Object
COB-ID: CAN object identification
Telegram: up to 4 words or 64 bits. The sum of the various objects must not exceed 8 words.
Evaluation of
the COB-ID
and data
transfer type
CANopen send telegram
PZD send word
(0)
p2051
[0]
PZD send word
(0)
p2051
[1]
PZD send word
(0)
p2051
[2]
PZD send word
(0)
p2051
[3]
PZD send word
(0)
p2051
[4]
PZD send word
(0)
p2051
[5]
PZD send word
(0)
p2051
[6]
PZD send word
(0)
p2051
[7]
Transmit PDO 1
0000 hex ... C000 06DF hex
p8720[0..4] (C000 06DF hex)
Mapping TPDO 1
0000 hex ... FFFF FFFF hex
p8730[0..3] (0000 hex)
Diag send word
r2053[0..7]

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals