Installing
3.2 Connecting
SINAMICS G120C, FSD ... FSF inverters
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
23
Table 3- 6 Permissible circuit-breakers (DIVQ)
Frame
size
Rated power
Inverter article num-
ber
Circuit breaker
SCCR
2)
Control
cabinet
3)
Article number
I
max
1)
FSD 22 kW 6SL3210-1KE24-4… NCGA, NDGB, FXD6-A,
FD6-A
70 A 35 kA, 480 V AC ≥ 36600 in³
LGGA, HCGA, HDGB,
LDGB, HFD6, HFXD6
70 A 65 kA, 480 VAC ≥ 36600 in³
CED6, HHFD6, HHFXD6,
CFD6
70 A 100 kA, 480 V AC ≥ 36600 in³
3RV1742
70 A
65 kA, 480Y / 277 V AC
4)
≥ 36600 in³
30 kW 6SL3210-1KE26-0… NCGA, NDGB, FXD6-A,
FD6-A
90 A 35 kA, 480 VAC ≥ 36600 in³
LGGA, HCGA, HDGB,
LDGB, HFD6, HFXD6
90 A 65 kA, 480 VAC ≥ 36600 in³
CED6, HHFD6, HHFXD6,
CFD6
90 A 100 kA, 480 V AC ≥ 36600 in³
37 kW 6SL3210-1KE27-0… NCGA, NDGB, NFGB,
FXD6-A, FD6-A
100 A 35 kA, 480 VAC ≥ 36600 in³
LGGA, HCGA, HDGB,
LDGB, HFGB, LFGB,
HFD6, HFXD6
100 A 65 kA, 480 VAC ≥ 36600 in³
CED6, HHFD6, HHFXD6,
CFD6
100 A 100 kA, 480 V AC ≥ 36600 in³
45 kW 6SL3210-1KE28-4… NCGA, NDGB, NFGB,
FXD6-A, FD6-A
125 A 35 kA, 480 V AC ≥ 36600 in³
LGGA, HCGA, HDGB,
LDGB, HFGB, LFGB,
HFD6, HFXD6
125 A 65 kA, 480 VAC ≥ 36600 in³
CED6, HHFD6, HHFXD6,
CFD6
125 A 100 kA, 480 V AC ≥ 36600 in³
FSE 55 kW 6SL3210-1KE31-1… NCGA, NDGB, NFGB,
FXD6-A, FD6-A
150 A 35 kA, 480 VAC ≥ 36600 in³
HCGA, HDGB, LDGB,
HFGB, HFD6, HFXD6
150 A 65 kA, 480 VAC ≥ 36600 in³
HHFD6, HHFXD6, CFD6
150 A
100 kA, 480 V AC
≥ 36600 in³