Installing
3.2 Connecting
SINAMICS G120C, FSD ... FSF inverters
24 Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
FSF 75 kW 6SL3210-1KE31-4… NFGB, FXD6-A, FD6-A,
JD6-A, JXD6-A
200 A 35 kA, 480 VAC ≥ 36600 in³
HFGB, LFGB, HFD6,
HFXD6, HJD6-A,
200 A 65 kA, 480 VAC ≥ 36600 in³
HHFD6, HHFXD6, CFD6,
HHJD6, HHJXD6,
200 A 100 kA, 480 V AC ≥ 36600 in³
90 kW 6SL3210-1KE31-7… NFGB, FXD6-A, FD6-A,
250 A 35 kA, 480 V AC ≥ 36600 in³
HFGB, LFGB, HFD6,
HFXD6, HJD6-A,
250 A 65 kA, 480 VAC ≥ 36600 in³
HHFD6, HHFXD6, CFD6,
HHJD6, HHJXD6,
250 A 100 kA, 480 V AC ≥ 36600 in³
110 kW 6SL3210-1KE32-1… NJGA, JD6-A, JXD6-A,
300 A 35 kA, 480 VAC ≥ 36600 in³
HJGA, LJGA, HJD6-A,
HJXD6-A, HLD6-A,
HLXD6-A, HHLD6,
300 A 65 kA, 480 VAC ≥ 36600 in³
HHJD6, HHJXD6,
300 A 100 kA, 480 V AC ≥ 36600 in³
132 kW 6SL3210-1KE32-4… NJGA, JD6-A, JXD6-A,
LD6-A, LXD6-A
350 A 35 kA, 480 VAC ≥ 36600 in³
HJGA, LJGA, HJD6-A,
HJXD6-A, HLD6-A,
HLXD6-A, HHLD6,
350 A 65 kA, 480 VAC ≥ 36600 in³
HHJD6, HHJXD6,
350 A 100 kA, 480 V AC ≥ 36600 in³
Maximum rated current of the circuit-breaker
Short circuit current rating of the inverter
Minimum envelope dimensions of a control cabinet approved according to UL in which the inverter is installed.
4)
65 kA, 480 VAC with rated current < 35 A