Installing
3.2 Connecting
SINAMICS G120C, FSD ... FSF inverters
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
25
Table 3- 7 Permissible Type E combination motor controller (NKJH)
Type E combination motor controller
FSD 22 kW 6SL3210-1KE24-4… 3RV2031-4WA1.. or
3RV2032-4WA1..
5)
52 A 40 HP 65 kA, 480Y / 277 VAC ≥ 36600 in³
3RV1041-4KA1.. or
3RV1042-4KA1..
6)
75 A 60 HP 65 kA, 480Y / 277 V AC ≥ 36600 in³
30 kW 6SL3210-1KE26-0… 3RV1041-4LA1.. or
90 A 75 HP 65 kA, 480Y / 277 VAC ≥ 36600 in³
37 kW 6SL3210-1KE27-0… 3RV1041-4MA1.. or
75 HP 65 kA, 480Y / 277 V AC ≥ 36600 in³
Maximum rated current of the Type E combination motor controller. You may use NKJH-listed Type E combination
motor controller of the same type - with a rated voltage ≥ 480 V AC and with a lower rated current - which match the in-
verter.
Rated power of the Type E combination motor controller at 460 V AC
Short circuit current rating of the inverter
Minimum envelope dimensions of a control cabinet approved according to UL in which the inverter is installed.
UL approval only with phase barrier 3RV2938-1K
6)
UL approval only with phase barrier 3RT1946-4GA07