Commissioning
4.2 Commissioning with BOP-2 operator panel
SINAMICS G120C, FSD ... FSF inverters
52 Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
Changing settings using BOP-2
You can modify the settings of your inverter by changing the values of the its parameters.
The inverter only permits changes to "write" parameters. Write parameters begin with a "P",
e.g. P45.
The value of a read-only parameter cannot be changed. Read-only parameters begin with an
"r", for example: r2.
To change write parameters using the BOP-2, proceed as follows:
Select the menu to display and
change parameters.
Press the OK key.
Select the parameter filter using the
arrow keys.
Press the OK key.
– STANDARD: The inverter only
displays the most important
parameters.
– EXPERT: The inverter displays
all of the parameters.
Select the required number of a write parameter using the arrow keys.
Select the value of the write parameter using the arrow keys.
Accept the value with the OK key.
You have now changed a write parameter using the BOP-2.
The inverter saves all the changes made using the BOP-2 so that they are protected against
power failure.
Changing indexed parameters
For indexed parameters, several parameter values are assigned to a parameter number.
Each of the parameter values has its own index.
To change an indexed parameter, proceed as follows:
Select the parameter number.
Set the parameter value for the selected index.
You have now changed an indexed parameter.